Chapter 14: The Transformer
Free practice questions on The Transformer, chapter 14 of the SARL's Class A manual, for South Africa's Radio Amateur Examination (RAE). Every question has the right answer and an explanation. Sections covered:
- 14.1 Theory of operation
- 14.2 Turns ratio
- 14.3 Voltage ratio
- 14.4 Current ratio
- 14.5 Impedance ratio
- 14.6 Applications
-
Show answer
Electromagnetic induction
AC in the primary sets up a changing magnetic field, which induces a voltage in the secondary: electromagnetic induction. Electrostatic induction is charge moved by an electric field, as between a capacitor’s plates.
-
Show answer
Inductive coupling through a changing magnetic field
The primary’s changing magnetic field passes through the secondary and induces a voltage in it, so the windings are coupled inductively. There is a little stray capacitance between windings, but that is not how the power gets across.
-
Show answer
A changing magnetic field passing through a conductor induces a voltage in it
A magnetic field that keeps changing induces a voltage in any conductor it passes through, here the turns of the secondary. A transformer does not work through an electric field, and a steady magnetic field induces nothing.
-
Show answer
No voltage of any kind
Steady DC makes a steady magnetic field, and only a changing field induces a voltage, so apart from a brief pulse at switch-on the secondary gives nothing. The turns ratio applies only to AC.
-
Show answer
Mutual inductance
The manual calls it mutual inductance, to set it apart from self inductance, in which a coil’s changing current induces a voltage in that same coil, the property that characterises an inductor.
-
Show answer
A fluctuating magnetic field
A current that keeps changing produces a magnetic field that keeps changing, and this fluctuating field is what induces the voltage in the secondary. A steady field would come only from a steady current.
-
Show answer
Changing the voltage and current of AC
A transformer changes the voltage and current of alternating current, raising one while lowering the other. Turning AC into DC is the job of a rectifier and smoothing, which in a power supply follow the transformer.
-
Show answer
A coil’s changing current inducing a voltage in that same coil
Self inductance is a single coil’s changing current inducing a voltage in that same coil, the property of an inductor. When one coil’s changing current induces a voltage in another coil, that is mutual inductance.
-
Show answer
The winding connected to the source of power
The primary is the winding that receives power from the source; the windings feeding loads are secondaries. It need not be the winding wound first: which is which depends only on how the transformer is connected.
-
Show answer
It does not: it makes no distinction
The symbol is just two coils side by side and does not show which is which; the primary is whichever winding the source feeds. Drawings often put the source on the left, but that is habit, not a rule.
-
Show answer
Yes; that winding then becomes the primary
In principle a transformer works both ways: whichever winding the source feeds is the primary. A step-down transformer fed from its low-voltage winding therefore steps the voltage up, provided its windings can take the voltages.
-
Show answer
Two
The winding fed by the source is the primary and every winding that feeds a load is a secondary, so this transformer has one primary and two secondaries; a transformer may have several secondaries.
-
Show answer
Two coils drawn side by side
The symbol shows the two windings as coils side by side, as they sit on their shared former, often with the turns ratio beside them. Coils drawn end to end look like inductors in series, and zigzags are resistors.
-
Show answer
Two or more coils wound on the same former
A transformer has two or more windings sharing a former, so the magnetic field of one passes through the others. Coils kept far apart would hardly couple, and plates with an insulator form a capacitor.
-
Show answer
The primary has twelve times as many turns as the secondary
The primary turns are always given first, so 12:1 means twelve primary turns for every secondary turn. It gives only the proportion: the windings might have 1 200 and 100 turns, or 2 400 and 200.
-
Show answer
6:1
The primary turns come first: 1 500 ÷ 250 = 6, so the ratio is 6:1. Writing 1:6 puts the secondary first and would describe a transformer with six times as many secondary turns.
-
Show answer
1 800 turns
In 1:15 the secondary has fifteen times the turns of the primary: NS = 120 × 15 = 1 800 turns. Dividing by 15 instead gives 8 turns, which would fit a 15:1 transformer.
-
Show answer
How many turns each winding actually has
A turns ratio compares the windings without giving their turns: 10:1 could be 200 and 20 turns or 5 000 and 500. As the primary is named first, it does show that the primary has more turns.
-
Show answer
1:7
The primary’s turns are written first, so a secondary with seven times the primary’s turns gives 1:7. Writing 7:1 would mean the primary has the extra turns, and the squared figures are not turns ratios at all.
-
Show answer
The 11:1 has more turns on its primary, the 1:11 more on its secondary
A turns ratio always gives the primary first, so 11:1 has eleven primary turns for each secondary turn and 1:11 the reverse. They are different transformers, though either could be used the other way round.
-
Show answer
2,5:1
NP ÷ NS = 500 ÷ 200 = 2,5, written 2,5:1 with the primary first; a turns ratio need not be a whole number. 1:2,5 turns it upside down, and 300:1 subtracts the turns instead of dividing them.
-
Show answer
As numbers written beside the symbol
The ratio is usually written in figures next to the symbol, such as 10:1. The loops drawn do not show the real number of turns, and the windings are neither shaded nor thickened.
-
Show answer
The transformer principle
The manual calls it the transformer principle: the primary and secondary voltages are in the ratio of the turns, VP ÷ VS = NP ÷ NS. Ohm’s law relates voltage, current and resistance in one component instead.
-
Show answer
How many turns the secondary has
NP and NS are the numbers of turns on the primary and the secondary, while the voltages are VP and VS and the currents IP and IS. The S stands for secondary, not supply: the supply feeds the primary.
-
Show answer
The ratio of primary turns to secondary turns
The voltages are in the same ratio as the turns, VP ÷ VS = NP ÷ NS, so the winding with more turns has the higher voltage. The inverted ratio is the usual slip; differences and products of turns mean nothing here.
-
Show answer
A step-up transformer
In 1:6 the secondary has six times the primary’s turns, and more secondary turns give a higher secondary voltage, so it steps the voltage up. A 6:1 transformer, with fewer secondary turns, would step it down.
-
Show answer
45 V
VS = VP × NS ÷ NP = 9 × 5 ÷ 1 = 45 V, since a 1:5 transformer steps up. 1,8 V comes from dividing by 5, reading the ratio upside down; 225 V squares the ratio.
-
Show answer
10 V
VS = VP × NS ÷ NP = 230 × 50 ÷ 1 150 = 10 V. Multiplying by 1 150 ÷ 50 instead turns the ratio upside down and gives 5,29 kV, a step-up that these turns cannot give.
-
Show answer
15 V
VS = VP × NS ÷ NP = 240 × 1 ÷ 16 = 15 V. Multiplying by 16 (3 840 V) reads the ratio upside down, and 0,94 V divides by 16², as if voltage followed the square of the turns ratio.
-
Show answer
14 V
VP = VS × NP ÷ NS = 42 × 1 ÷ 3 = 14 V; the secondary has three times the turns, so three times the voltage. Multiplying by 3 (126 V) applies the ratio the wrong way round.
-
Show answer
5:1
NP ÷ NS = VP ÷ VS = 230 ÷ 46 = 5, so the ratio is 5:1, primary first. 1:5 would describe a step-up transformer, and squared figures such as 25:1 belong to impedances, not voltages.
-
Show answer
13 V
VS = VP × NS ÷ NP = 230 × 52 ÷ 900 = 13,3 V, so 13 V is nearest. 4 kV comes from multiplying by 900 ÷ 52, the ratio upside down, and 0,8 V squares the ratio.
-
Show answer
220 V
VS = VP × NS ÷ NP = 38 × 6 ÷ 1 = 228 V, so 220 V is nearest. 6,3 V comes from dividing by 6, reading the step-up ratio upside down, and 1,4 kV multiplies by 6².
-
Show answer
2 A
IS = IP × NP ÷ NS = 0,5 × 4 ÷ 1 = 2 A: a step-down transformer delivers more current than it draws. 125 mA comes from dividing by 4, which is the voltage rule used for current.
-
Show answer
3 A
IS ÷ IP = NP ÷ NS, so IP = IS × NS ÷ NP = 0,3 × 10 ÷ 1 = 3 A; a step-up transformer draws more current than it delivers. 30 mA applies the ratio the wrong way round.
-
Show answer
It is smaller, by the turns ratio
Current changes the opposite way to voltage, IS ÷ IP = NP ÷ NS. A step-up transformer raises the voltage, so its secondary current is smaller, which keeps the power out equal to the power in.
-
Show answer
The secondary winding
Current changes the opposite way to voltage. A step-down transformer lowers the voltage, so its secondary carries the larger current: a 10:1 transformer drawing 1 A from the supply gives 10 A to the load.
-
Show answer
4 A
IS = IP × NP ÷ NS = 0,25 × 1 400 ÷ 90 = 3,89 A, so 4 A is nearest. 16 mA comes from multiplying by 90 ÷ 1 400, the voltage rule used for current.
-
Show answer
It doubles as well
IS = IP × NP ÷ NS, so with the turns fixed the primary current is in proportion to the secondary current: the load decides what the primary draws, and twice the load current means twice the primary current.
-
Show answer
20:1
IS ÷ IP = NP ÷ NS, so NP ÷ NS = 4 ÷ 0,2 = 20, giving 20:1: a step-down transformer, with more current out than in. 1:20 is the voltage rule applied to the currents.
-
Show answer
2 A
IP = IS × NS ÷ NP = 0,4 × 1 000 ÷ 200 = 2 A: five times the turns on the secondary means one fifth of the current there. 80 mA divides by 5 instead, the ratio the wrong way round.
-
Show answer
Exactly the same amount
Power out equals power in, apart from minor losses, so when a transformer raises the voltage it lowers the current in the same proportion. The turns ratio changes voltage and current, never the power.
-
Show answer
30 W
An ideal transformer passes on all the power it draws: PP = PS = VS × IS = 12 × 2,5 = 30 W. Dividing by the turns ratio (2 W) treats power like voltage, but the turns ratio never changes the power.
Try it: Ohm's Law & Power -
Show answer
5 A
With no losses the secondary passes on the full 60 W, so IS = PS ÷ VS = 60 ÷ 12 = 5 A. Dividing 12 by 60 gives 0,2 A, the formula turned upside down.
Try it: Ohm's Law & Power -
Show answer
Eddy currents flowing in the core
The manual names winding resistance and eddy currents, currents induced in the core itself, as the causes of the small losses. Stray capacitance between turns exists but is not where the power goes.
-
Show answer
The resistance of its windings
Current through the windings’ resistance turns some power into heat in the copper, and eddy currents heat the core; together they make up the few per cent a practical transformer loses. Capacitance is not a main cause.
-
Show answer
In the transformer’s core
Eddy currents are induced in the core by its changing magnetic field and heat it, while the windings lose power through their resistance instead. Neither the mains cable nor the surrounding air carries them.
-
Show answer
Over 95%
Power transformers are typically more than 95% efficient, losing under 5% of the power in winding resistance and core eddy currents, so a figure such as 75% would be poor. Calculations often treat them as ideal.
-
Show answer
180 W
Efficiency = power out ÷ power in, so power out = 0,9 × 200 = 180 W, and the other 20 W is lost as heat. 200 W forgets the efficiency, treating the transformer as perfect.
-
Show answer
50 W
Power in = power out ÷ efficiency = 40 ÷ 0,8 = 50 W, of which 10 W is lost. Multiplying by 0,8 gives 32 W, less than the load itself takes, which no transformer can manage.
-
Show answer
90%
Efficiency = power out ÷ power in × 100% = 225 ÷ 250 × 100% = 90%; the missing 25 W is lost in the windings and the core. Dividing the other way round gives 111%, which is impossible.
-
Show answer
250 W
Power in = 240 × 1,2 = 288 W, and power out = 0,85 × 288 = 244,8 W, so 250 W is nearest. 290 W forgets the efficiency, treating the transformer as perfect.
Try it: Ohm's Law & Power -
Show answer
Transformers change AC voltages simply and efficiently
Transformers raise AC to very high voltages for long-distance lines and lower it again near users, simply and with little loss: the principal reason mains supplies are AC. AC is no safer to touch than DC.
-
Show answer
The lower current keeps heating in the lines small
For a given power, a higher voltage means a lower current, and the heating in a line’s resistance depends on the current. Long-distance lines therefore run at up to about 800 kV, where the current is comparatively small.
-
Show answer
Heating losses in the lines
Heating in a line depends on the current through its resistance, so a low current keeps those losses small. It also loses less voltage on the way, so the far end gets more, not less.
-
Show answer
Lower voltages are far safer for people to use
Very high voltages suit long-distance lines but are dangerous, so for safety the voltage is lowered near the user, to about 11 kV and then the mains voltage. The lines lose only a little voltage; transformers do the lowering.
-
Show answer
About 11 kV
The manual gives around 11 kV for local distribution; the long-distance network runs at up to about 800 kV, and a final transformer brings the 11 kV down to the customer’s mains voltage.
-
Show answer
460 Ω
RP = VP ÷ IP = 230 ÷ 0,5 = 460 Ω, an apparent resistance set by the load, not the winding’s own resistance, which is far smaller. Dividing the other way round gives 2,17 mΩ.
Try it: Ohm's Law & Power -
Show answer
In the load connected to the secondary
An ideal transformer dissipates nothing itself: the power passes through it to the load, where it is dissipated. That is why the resistance the supply sees at the primary is only an apparent one.
-
Show answer
Impedance transformation
The load resistance is changed by the transformer just as its voltage and current are, and appears at the primary as a related value: impedance transformation. Impedance matching is a use made of it.
Try it: DIY Components -
Show answer
Resistance and reactance
Impedance combines resistance with reactance, the frequency-dependent opposition of inductors and capacitors to AC. Inductance, in henrys, is only one source of reactance, and capacitance provides the other.
-
Show answer
Through the square of the turns ratio
RP = RL × (NP ÷ NS)²: the voltage is multiplied by the turns ratio and the current divided by it, so their quotient, the resistance, changes by the ratio squared. Using the plain ratio is the usual slip.
Try it: DIY Components -
Show answer
The load resistance is smaller
Resistance is transformed in the same direction as voltage, so a step-down transformer has the smaller voltage and the smaller resistance on its secondary: a 0,6 Ω load behind a 20:1 transformer looks like 240 Ω.
Try it: DIY Components -
Show answer
450 Ω
RP = RL × (NP ÷ NS)² = 50 × 3² = 450 Ω. Multiplying by 3 alone gives 150 Ω, forgetting that impedance follows the square of the turns ratio.
Try it: DIY Baluns & Ununs -
Show answer
800 Ω
RL = RP × (NS ÷ NP)² = 50 × 4² = 800 Ω, since a step-up transformer steps resistance up as well. Multiplying by 4 instead of 4² = 16 gives 200 Ω, the plain turns ratio.
Try it: DIY Components -
Show answer
6,32:1
The impedance ratio is 600 ÷ 15 = 40, and the turns ratio is its square root: √40 = 6,32, so 6,32:1. Using 40:1 as the turns ratio would transform the impedance 1 600 times.
Try it: DIY Components -
Show answer
3:1
The impedance ratio is 400 ÷ 50 = 8, and the turns ratio is √8 = 2,83, so 3:1 is nearest. 8:1 is the impedance ratio itself, not its square root, and 1:3 would make the 50 Ω look smaller, about 5,6 Ω.
Try it: DIY Components -
Show answer
38,4 kΩ
The other winding has 8 times the turns, so it works at 8² = 64 times the impedance: 600 × 64 = 38,4 kΩ. Multiplying by 8 alone (4,8 kΩ) uses the turns ratio where its square belongs.
Try it: DIY Components -
Show answer
600 Ω
RP = RL × (NP ÷ NS)² = 75 × (400 ÷ 140)² = 75 × 8,16 = 612 Ω, so 600 Ω is nearest. Forgetting to square the turns ratio gives 214 Ω, hence the 210 Ω option.
Try it: DIY Components -
Show answer
9:1
Impedance follows the square of the turns ratio, so 3:1 in turns gives 3² = 9:1 in impedance, with the higher impedance on the primary. Quoting 3:1 for the impedance is the plain-ratio slip.
Try it: DIY Baluns & Ununs -
Show answer
2:1
NP ÷ NS = √(RP ÷ RL) = √(200 ÷ 50) = √4 = 2, so 2:1. A 4:1 turns ratio would raise the 50 Ω to 4² × 50 = 800 Ω, since impedance follows the square.
Try it: DIY Baluns & Ununs -
Show answer
200 Ω
RP = RL × (NP ÷ NS)² = 800 × (1 ÷ 2)² = 800 ÷ 4 = 200 Ω; a step-up transformer makes its load look smaller at the primary. Dividing by 2 alone gives 400 Ω.
Try it: DIY Components -
Show answer
50 Ω
RP = RL × (NP ÷ NS)² = 12,5 × 2² = 50 Ω, so turns in the ratio 2:1 give a 4:1 impedance step, as in a 4:1 balun. Doubling instead of multiplying by 4 gives 25 Ω.
Try it: DIY Baluns & Ununs -
Show answer
1:4,5
NP ÷ NS = √(50 ÷ 1 100) = √(1 ÷ 22) = 1 ÷ 4,69, so 1:4,5 is nearest, a step-up. 1:22 is the impedance ratio, not its square root.
Try it: DIY Components -
Show answer
It is generally much higher
A typical receiver’s RF amplifier has an input impedance well above, not below, the usual 50 Ω of an antenna system, so a transformer is often fitted to match the two and transfer the most power.
-
Show answer
When the load impedance equals the source impedance
A source delivers the most power when the load impedance equals its own, which is why transformers are used to match the two. A far higher load impedance draws less current and so takes less power.
-
Show answer
It lowers the mains voltage to suit the equipment
The mains voltage is far too high for 12 V equipment, so the transformer steps it down; a rectifier and smoothing circuit then turn the low AC voltage into the DC that the equipment needs.
Sign up free to save your score and see your progress in every chapter. You do not need to be a club member.